Available

Integrate. Don’t rip and replace

Ozari connects to the field devices and enterprise systems you already run, through a fault-isolated gateway and one open data layer. Every value carries its quality and its time, so people and AI can trust it.

  • IEC 61850
  • IEC 60870-5-104
  • DNP3
  • Modbus TCP
  • MQTT Sparkplug B
  • OPC UA
  • CIM / CGMES
  • ICCP / TASE.2
  • Syslog and CEF
  • InfluxDB line protocol
  • Prometheus
  • OIDC

Protocols

Honest status, protocol by protocol

We label each one by how far it has been proven. Lab-grade means tested against reference servers, not yet in the field.

ProtocolUsed forStatus
IEC 61850 (MMS)Substation automationVia certified stack Lab-proven against a reference server. GOOSE and sampled values are out of scope.
IEC 60870-5-104TelecontrolNative, lab-grade Passes 18 of 18 conformance tests. A certified stack is also verified.
DNP3TelecontrolVia certified stack Control proven in the lab. Production needs a commercial stack licence.
Modbus TCPInverters, meters, battery gatewaysNative, lab-grade Monitor and control.
MQTT Sparkplug BEdge gatewaysNative, lab-grade Monitor only.
OPC UAPlant and industrial systemsIn development Through the gateway and a certified stack.
ICCP / TASE.2Peer control centresLab-grade model Transport through a certified stack, in development.
CIM / CGMESNetwork modelsBuilt Core-class import and export, round-trip tested.
IEEE 2030.5 (CSIP-AUS)Customer solar and batteries in AustraliaNot supported Ozari does not connect to CSIP-AUS utility servers today. DER control runs through Modbus gateways.

Architecture

Why a separate gateway

Fault isolation

Certified vendor stacks run in their own process. If one crashes, the control plane keeps running.

Certification stays intact

Vendor stacks keep their certification, and the control plane stays small and pure Go.

Clean zoning

Gateways sit in their own zone, near the field. Links to the control plane use TLS or mutual TLS.

Data out

Your data, in the systems you already use

Historian

InfluxDB line protocol and file export. PI, AVEVA or Timescale connect through the same interface as a project integration.

Security analytics

Audit and security events as RFC 5424 syslog or CEF, over UDP or TCP, for the security platform you use.

Network models

CIM/CGMES export for planning and GIS tools, plus JSON.

Monitoring

Prometheus metrics, alert rules and a ready-made Grafana dashboard.

Peer control centres

ICCP/TASE.2 object model for data exchange with other control centres (lab-grade).

Operator console

A REST API for control and a live event stream for the console.

Commissioning

One point list, not two

The gateway can supply the tag-to-I/O map, so your engineers do not keep two copies in step. Each point carries its address, scale, offset and quality.

  • A/B field-link redundancy for gateways that support it.
  • Quality on every value: good, stale, bad or substituted.
  • Network models imported from CIM/CGMES or JSON.
  • A field simulator for testing the full path before site work.

Start safely

Begin with a read-only shadow pilot

Ozari runs beside your current systems, sees the same data and issues no commands. You measure the value with your own data before anything changes.